Advertisement

Operating Guide ECL Comfort 210/296/310, application A237/A337
MENU > Settings > Flow / power limit
Units
Choice of units for measured values.
See Appendix "Parameter ID overview"
Units to the left: pulse value.
Units to the right: actual and limitation values.
The value from the flow meter is expressed as ml or l.
The value from the energy meter is expressed as Wh, kWh, MWh
or GWh.
The values for the actual flow and the flow limitation are expressed
as l/h or m³/h.
The values for the actual power and the power limitation are
expressed as kW, MW or GW.
MENU > Settings > Flow / power limit
High limit Y2 (flow / power limitation, high limit, Y-axis)
Set the flow / power limitation referring to the outdoor temperature set
in 'Low T out X2' .
See Appendix "Parameter ID overview"
The corresponding X coordinate is set in 'Low T out X2' .
VI.LG.R3.02
1x115
List for setting range of 'Units':
ml, l/h
l, l/h
ml, m³/h
l, m³/h
Wh, kW
kWh, kW
kWh, MW
MWh, MW
MWh, GW
GWh, GW
Example 1:
'Units' (11115):
'Pulse' (11114):
Each pulse represents 10 litres and the flow is expressed as cubic
meters (m³) per hour.
Example 2:
'Units' (11115):
'Pulse' (11114):
Each pulse represents 1 kilo Watt hour and the power is
expressed in kilo Watt.
List for setting range of 'Units' when M-bus connection to flow or
energy meter:
l / h
m³/h
kW
MW
GW
1x116
l, m³/h
10
kWh, kW (= kilo Watt hour, kilo Watt)
1
© Danfoss | 2017.05 | 71