Danfoss ECL Comfort 210 Operating Manual page 95

Application a237/a337
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A237/A337
5.9.1 Differentiated heat cut-out
To set differentiated cut-out parameters for a heating circuit for
"Summer" and "Winter" go to "Heat cut-out":
(MENU > Settings > Heat cut-out)
This function is active when the dates for "Summer" and "Winter"
are different in the "Heat cut-out" menu.
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Heat cut-out
Extended heat cut-out setting
Parameter
ID
1x393
Summer day
1x392
Summer month
1x179
Summer cut-out
1x395
Summer filter
See Appendix "Parameter ID overview"
MENU > Settings > Heat cut-out
Extended winter cut-out setting
Parameter
ID
1x397
Winter day
1x396
Winter month
1x398
Winter cut-out
1x399
Winter filter
See Appendix "Parameter ID overview"
The above settings of the dates for the cut-out function are only
to be done in the heating circuit 1 and are valid for other heating
circuits in the controller as well, if applicable.
The cut-out temperatures as well as the filter constant are to be set
individually per heating circuit.
VI.LG.R3.02
Setting range
Factory
setting
*
*
*
*
*
*
*
*
Setting range
Factory
setting
*
*
*
*
*
*
*
*
The heating cut-out is only active when the controller mode is in
scheduled operation. When the cut-out value is set to OFF, there is
no heating cut-out.
© Danfoss | 2017.05 | 95

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl comfort296Ecl comfort 310

Table of Contents