MENU > Settings > Return limit
Limit (return temp. limitation)
Set the return temperature value you accept for the system.
See Appendix "Parameter ID overview"
When the return temperature falls below or gets higher than the
set value, the controller automatically changes the desired flow /
duct temperature to obtain an acceptable return temperature. The
influence is set in 'Infl. - max.' and 'Infl. - min.' .
MENU > Settings > Return limit
High T out X1 (return temp. limitation, high limit, X-axis)
Set the outdoor temperature value for the low return temperature limitation.
See Appendix "Parameter ID overview"
The corresponding Y coordinate is set in 'Low limit Y1' .
MENU > Settings > Return limit
Low limit Y1 (return temp. limitation, low limit, Y-axis)
Set the return temperature limitation referring to the outdoor temperature
value set in 'High T out X1' .
See Appendix "Parameter ID overview"
The corresponding X coordinate is set in 'High T out X1' .
MENU > Settings > Return limit
Low T out X2 (return temp. limitation, low limit, X-axis)
Set the outdoor temperature value for the high return temperature
limitation.
See Appendix "Parameter ID overview"
The corresponding Y coordinate is set in 'High limit Y2' .
MENU > Settings > Return limit
High limit Y2 (return temp. limitation, high limit, Y-axis)
Set the return temperature limitation referring to the outdoor temperature
value set in 'Low T out X2' .
See Appendix "Parameter ID overview"
The corresponding X coordinate is set in 'Low T out X2' .