Operating Guide ECL Comfort 210/296/310, application A237/A337
MENU > Settings > Application
Max. DHW time
Set the max DHW heating time (minutes). When DHW heating is active and
the set 'Max. DHW time' expires, DHW heating is deactivated.
See Appendix "Parameter ID overview"
OFF:
If the DHW temperature is lower than the DHW charging
cut-in temperature, the DHW charging remains active
for unlimited period of time. If the DHW temperature is
higher than the DHW charging cut-in temperature, the
charging is deactivated after 35 minutes.
Value:
The DHW heating / charging is deactivated when the set
'Max. DHW time' (in minutes) expires.
MENU > Settings > Application
DHW deact. time (DHW deactivation time)
Set the time (minutes) that must elapse after a DHW heating period before a
new DHW heating period can be started.
See Appendix "Parameter ID overview"
Value:
When the DHW heating / charging time has reached its
maximum, DHW can only be heated / charged again
after the set deactivation time (in minutes) has expired.
MENU > Settings > Application
P demand
The circulation pump in the master circuit can be controlled in relation to
the master circuit's demand or slave circuit's demand.
See Appendix "Parameter ID overview"
Heating applications:
OFF:
The circulation pump is ON when the desired flow
temperature in the heating circuit is higher than the
value set in 'P heat T' .
ON:
The circulation pump is ON when the desired flow
temperature from slaves is higher than the value set in
'P heat T' .
Cooling applications:
OFF:
The circulation pump is ON when the desired flow
temperature in the cooling circuit is lower than the value
set in 'P cool T' .
ON:
The circulation pump is ON when the desired flow
temperature from slaves is lower than the value set in
'P cool T' .
86 | © Danfoss | 2017.05
1x044
1x045
1x050
The circulation pump is always controlled according to frost protection
conditions.