Danfoss ECL Comfort 210 Operating Manual page 7

Application a237/a337
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A237/A337
A237.1, ex. a, A337.1, ex. a
During DHW heating, the circulation pump P1 in the heating circuit
can:
be switched OFF (DHW priority mode)
or
remain ON, as long as the heating temperature at S3 does not
differ more than a set value from the desired temperature
(dependent parallel mode)
or
be continuously ON. This means same temperature in the
heating circuit as the DHW heating temperature (parallel
mode).
A237.1 used in ECL 296 / 310
The flow / power signal can come as a pulse signal or an M-bus
signal.
A337.1
The desired flow temperature of the heating circuit can, via S10, be
controlled by means of an external voltage in the range 0 - 10 volt.
Modbus communication to a SCADA system can be established.
A connected flow or energy meter based on M-bus signal can
limit the flow or power to a set maximum value. Furthermore, the
limitation can be in relation to the outdoor temperature.
Typically, the lower the outdoor temperature, the higher the
accepted flow / power.
M-bus data can be transferred to the Modbus communication.
Heating in general
Exercise of circulation pumps and control valve in periods without
heating demand can be arranged.