Danfoss ECL Comfort 210 Operating Manual page 101

Application a237/a337
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A237/A337
MENU > Settings > Tank temperature
Start difference
Set the number of degrees below the desired DHW temperature that will
start the DHW heating (charging).
See Appendix "Parameter ID overview"
Value:
Set the number of degrees.
VI.LG.R3.02
1x195
=
X
Time
# 1 # =
Charging difference (ID 1x193)
# 2 # =
Desired DHW temperature
# 3 # =
Start difference (ID 1x195)
# 4 # =
Actual DHW temperature
# 5# =
DHW heating / charging activity
Example:
Desired DHW temp.:
Start difference:
Result:
The DHW heating starts when the temperature measured by the tank
temperature sensor (upper) is lower than 52 °C.
55 °C
-3 K
© Danfoss | 2017.05 | 101