Danfoss ECL Comfort 210 Operating Manual page 119

Application a237/a337
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A237/A337
MENU > Common controller > System > M-bus config.
Command
Circuit
-
NONE / INIT / SCAN / GATEW
The ECL Comfort 296 / 310 / 310B are M-bus masters. In order to verify
connected energy meters, different commands can be activated.
NONE:
No command activated
INIT:
Initialization is activated
SCAN:
Scanning is activated in order to search for connected
energy meters. The ECL Comfort 296 / 310 / 310B
detect the M-bus addresses of up to 5 connected
energy meters and place these automatically in the
"Energy meters" section. The verified address is placed
after "Energy meter 1 (2, 3, 4, 5)"
GATEW: The ECL Comfort 296 / 310 / 310B act as a gateway
between energy meters and ECL Portal. Used only for
service.
MENU > Common controller > System > M-bus config.
M-bus address
Energy meter 1 (2, 3, 4, 5)
Circuit
-
The set or verified address of energy meter 1 (2, 3, 4, 5).
0:
Normally not used
1 - 250:
Valid M-bus addresses
251 - 254: Special functions. Use only M-bus address 254 when
one energy meter is connected.
255:
Not used
MENU > Common controller > System > M-bus config.
Type
Energy meter 1 (2, 3, 4, 5)
Circuit
-
Selecting data range from the M-bus telegram..
0:
Small data set, small units
1:
Small data set, large units
2:
Large data set, small units
3:
Large data set, large units
4:
Volume and energy data only
(example: HydroPort Pulse)
VI.LG.R3.02
5998
Setting range
Factory setting
NONE
6000
Setting range
Factory setting
0 - 255
6001
Setting range
Factory setting
0 - 4
Scan time can take up to 12 minutes.
When all energy meters are found, the command can be changed
to INIT or NONE.
255
Data examples:
0:
Flow temp., return temp., flow, power, acc. volume, acc. energy.
0
3:
Flow temp., return temp., flow, power, acc. volume, acc. energy,
tariff 1, tariff 2.
See also the "Instructions, ECL Comfort 210 / 310, communication
description" for further details.
See also Appendix for detailed description of "Type".
© Danfoss | 2017.05 | 119

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl comfort296Ecl comfort 310

Table of Contents