Operating Guide ECL Comfort 210/296/310, application A237/A337
MENU > Settings > Application
Demand offset
The desired flow temperature in heating circuit 1 can be influenced by the
demand for a desired flow temperature from another controller (slave) or
another circuit.
See Appendix "Parameter ID overview"
OFF:
The desired flow temperature in circuit 1 is not
influenced by the demand of any other controller (slave
or circuit 2).
Value: The desired flow temperature is increased by the set
value in 'Demand offset' , if the demand of the slave /
circuit 2 is higher.
MENU > Settings > Application
P exercise (pump exercise)
Exercises the pump to avoid blocking in periods without heat demand.
See Appendix "Parameter ID overview"
OFF:
The pump exercise is not active.
ON:
The pump is switched ON for 1 minute every third day at
noon (12:14 hours).
84 | © Danfoss | 2017.05
Heating application
1x017
=
X
Time
=
Y
Desired flow temperatures
=
# 1 #
Demand offset
=
# 2 #
Desired flow temperature, master
=
# 3 #
Desired flow temperature, slave
The function of 'Demand offset' can compensate for heat losses
between master and slave controlled systems.
'Demand offset' with a value is to be used in the Master controller only.
When setting "Demand offset" to a value, the return temperature
limitation will react according to the highest limitation value (Heating
/ DHW).
1x022
VI.LG.R3.02