ECA MENU > ECA system > ECA override
Override circuit
Setting range
OFF / 1 ... 4
The feature 'Override' (to extended comfort or
saving period or holiday) must be addressed to the
heating circuit in question.
OFF:
No heating circuit is selected for override.
1 ... 4: The heating circuit number in question.
ECA MENU > ECA system > ECA version
ECA version (read-out only), examples
087H3200
Code no.
Hardware
A
1.42
Software
5927
Build no.
13579
Serial no.
23.2012
Production week
The ECA version information is useful in service situations.
VI.LG.R3.02
Factory setting
OFF
The circuit in question for override in the ECL controller must be in
scheduled mode.
See also the parameter 'Override addr.' .
Example 1:
(One ECL controller and one ECA 30 / 31)
Override of heating
Set 'Connection addr.' to
circuit 2:
15
Example 2:
(Several ECL controllers and one ECA 30 / 31)
Override of heating
Set 'Connection addr.' to 6 Set 'Override
circuit 1 in ECL
controller with the
address 6:
Quick guide "ECA 30 / 31 to override mode":
1. Go to ECA MENU
2. Move cursor to "Clock" symbol
3. Select the "Clock" symbol
4. Choose and select one of 4 override functions
5. Below the override symbol: Set hours or date
6. Below hours / date: Set desired room temperature for the override
period
Set 'Override
circuit' to 2
circuit' to 1
© Danfoss | 2017.05 | 129