Danfoss ECL Comfort 210 Operating Manual page 69

Application a237/a337
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A237/A337
DHW circuit
A flow or heat meter can be connected to the ECL controller in
order to limit the flow or consumed power. The signal from the
flow or heat meter is a pulse signal.
When the application runs in an ECL Comfort 296 / 310 controller,
the flow / power signal can be obtained from a flow / heat meter
via the M-bus connection.
When the flow / power gets higher than the calculated limit, the
controller gradually reduces the desired flow temperature to obtain
an acceptable max. flow or power consumption.
The parameter 'Units' (ID 1x115) has a reduced setting range when
the flow / energy signal comes via M-bus.
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Flow / power limit
Input type
Choice of input type from flow / energy meter
See Appendix "Parameter ID overview"
OFF:
No input
IM1 -
Flow / energy meter signal based on pulses.
IM5:
EM1 -
Flow / energy meter signal from M-bus.
EM5:
VI.LG.R3.02
=
X
Time
=
Y
Flow or power
# 1 # =
Flow or power limit
# 2 # =
Actual flow or energy
# 3 # =
Desired flow temperature
Pulse based signal for flow / power, applied to input S7
For monitoring:
Frequency range is 0.01 - 200 Hz
For limitation:
Minimum frequency is recommended to be 1 Hz in order to have a
stable control. Furthermore, the pulses must appear regularly.
1x109
The setting range for IM and EM depends on chosen subtype.
© Danfoss | 2017.05 | 69