Danfoss ECL Comfort 210 Operating Manual page 72

Application a237/a337
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A237/A337
MENU > Settings > Flow / power limit
Low limit Y1 (flow / power limitation, low limit, Y-axis)
Set the flow / power limitation referring to the outdoor temperature set in
'High T out X1' .
See Appendix "Parameter ID overview"
The corresponding X coordinate is set in 'High T out X1' .
MENU > Settings > Flow / power limit
Low T out X2 (flow / power limitation, low limit, X-axis)
Set the outdoor temperature value for the high flow / power limitation.
See Appendix "Parameter ID overview"
The corresponding Y coordinate is set in 'High limit Y2' .
MENU > Settings > Flow / power limit
High T out X1 (flow / power limitation, high limit, X-axis)
Set the outdoor temperature value for the low flow / power limitation.
See Appendix "Parameter ID overview"
The corresponding Y coordinate is set in 'Low limit Y1' .
72 | © Danfoss | 2017.05
1x117
The limitation function can overrule the set 'Temp. min' of the desired
flow temperature.