Danfoss ECL Comfort 210 Operating Manual page 121

Application a237/a337
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A237/A337
6.8.8 Sensor offset (new functionality as from firmware 1.59)
The measured temperature can be offset adjusted in order to
compensate for cable resistance or a not-optimum place for the
temperature sensor. The adjusted temperature can be seen in "Raw
input overview" and "Input overview".
Common controller > System > Sensor offset
Sensor 1 . . . (temperature sensor)
Circuit
Setting the offset of the measured temperature.
Positive
The temperature value is increased
offset
value:
Negative
The temperature value is decreased
offset
value:
6.8.9 Display
Backlight (display brightness)
Circuit
Adjust the brightness of the display.
0:
Weak backlight.
10:
Strong backlight.
Contrast (display contrast)
Circuit
Adjust the contrast of the display.
0:
Low contrast.
10:
High contrast.
6.8.10 Communication
Modbus addr.
Circuit
Set the Modbus address if the controller is part of a Modbus
network.
1 ... 247: Assign the Modbus address within the stated setting
range.
VI.LG.R3.02
Setting range
Factory setting
*
60058
Setting range
Factory setting
0 ... 10
60059
Factory setting
Setting range
0 ... 10
38
Setting range
Factory setting
1 ... 247
*
5
3
The Application Key A214 (subtypes A214.1 . . . A214.6 and A314.1
1
. . . A314.3) is also able to communicate via Modbus to Danfoss
ADAP-KOOL® Service Manager.
© Danfoss | 2017.05 | 121