Operating Guide ECL Comfort 210/296/310, application A237/A337
Example 2
ECL in Comfort mode, but in Saving mode at override.
Choose an unused input, for example S8. Connect the override
switch or override relay contact.
Settings in ECL:
1. Select circuit > MENU > Settings > Application > Ext. input:
Select the input S8 (the wiring example)
2. Select circuit > MENU > Settings > Application > Ext. mode:
Select SAVING
3. Select circuit > MENU > Schedule:
Select all weekdays
Set "Start1" to 00.00
Set "Stop1" to 24.00
Exit menu and confirm by "Save"
4. Remember to set the circuit in question in scheduled mode
("clock").
Result: When the override switch (or the relay contact) is ON, the
ECL 210 / 296 / 310 will operate in Saving mode.
When the override switch (or the relay contact) is OFF, the ECL 210
/ 296 / 310 will operate in Comfort mode.
Example 3
The week schedule for the building is set with comfort periods
Monday - Friday: 07.00 - 17.30. Sometimes, a team meeting takes
place in the evening or in the week-end.
An override switch is installed and heating must be ON (Comfort
mode) as long as the switch is ON.
Choose an unused input, for example S8. Connect the override
switch.
Settings in ECL:
1. Select circuit > MENU > Settings > Application > Ext. input:
Select the input S8 (the wiring example)
2. Select circuit > MENU > Settings > Application > Ext. mode:
Select COMFORT
3. Remember to set the circuit in question in scheduled mode
("clock").
Result: When the override switch (or a relay contact) is ON, the ECL
210 / 296 / 310 will operate in Comfort mode.
When the override switch is OFF, the ECL 210 / 296 / 310 will
operate according to the schedule.
VI.LG.R3.02
# 1 # = Override switch or relay contact (not activated / activated)
# 2 # = Function mode (Schedule / Saving)
# 3 # = Time
# 1 # = Override switch (not activated / activated)
# 2 # = Function mode (Schedule / Comfort)
# 3 # = Time
© Danfoss | 2017.05 | 133