Operating Guide ECL Comfort 210/296/310, application A237/A337
2.6.2 ECL Application Key, copying data
General principles
When the controller is connected and operating, you can check
and adjust all or some of the basic settings. The new settings can
be stored on the Key.
How to update the ECL Application Key after settings have
been changed?
All new settings can be stored on the ECL Application Key.
How to store factory setting in the controller from the
Application Key?
Please read the paragraph concerning Application Key, Situation
1: The controller is new from the factory, the ECL Application Key
is not inserted.
How to store personal settings from the controller to the Key?
Please read the paragraph concerning Application Key, Situation 3:
A copy of the controllers settings is needed for configuring another
controller
As a main rule, the ECL Application Key should always remain in
the controller. If the Key is removed, it is not possible to change
settings.
VI.LG.R3.02
Factory settings can always be restored.
Make a note of new settings in the 'Settings overview' table.
Do not remove the ECL Application Key while copying. The data on
the ECL Application Key can be damaged!
It is possible to copy settings from one ECL Comfort controller to
another controller provided that the two controllers are from the same
series (210 or 310).
Furthermore, when the ECL Comfort controller has been uploaded
with an application key, minimum version 2.44, it is possible to upload
personal settings from application keys, minimum version 2.14.
The "Key overview" does not inform — through ECA 30 / 31 — about
the subtypes of the application key.
Key inserted / not inserted, description:
ECL Comfort 210 / 310, controller versions lower than 1.36:
-
Take out the application key; for 20 minutes
settings can be changed.
-
Power up the controller without the
application key inserted; for 20 minutes
settings can be changed.
ECL Comfort 210 / 310, controller versions 1.36 and up:
-
Take out the application key; for 20 minutes
settings can be changed.
-
Power up the controller without the
application key inserted; settings cannot be
changed.
ECL Comfort 296 , controller versions 1.58 and up:
-
Take out the application key; for 20 minutes
settings can be changed.
-
Power up the controller without the
application key inserted; settings cannot be
changed.
© Danfoss | 2017.05 | 35