See also the related Installation Guide (find it on http://heating.danfoss.com ) for description of the functions. The Application Keys comply with ECL Comfort 210 / 296 / 310 controllers as of software version 1.11 (visible at start-up of the controller and in 'Common controller settings' in 'System').
Page 3
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program Safety Note To avoid injury of persons and damages to the device, it is absolutely necessary to read and observe these instructions carefully. Necessary assembly, start-up, and maintenance work must be performed by qualified and authorized personnel only.
Page 4
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program °C (degrees Celsius) is a measured temperature value whereas K (Kelvin) often is used for temperature differences. The ID no. is unique for the selected parameter. Example First digit...
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program 2.0 Installation 2.1 Description, in general Application keys for the ECL Comfort 210 / 296 / 310 series, which control heating circuits, offer a floor drying program, also called screed drying program.
Page 6
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program When the floor drying process is finished, a data log can be read from the ECL Comfort controller by means of the "ECL Tool". The data log can be used for documenting the process.
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program 3.0 Settings 3.1 Parameters and descriptions Parameter tables contain parameter name, ID and descriptions. Parameters’ setting range and factory settings are listed in the section "Parameter ID overview" at the end of this Operating Guide.
Page 8
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program Desired flow T (Desired flow temperature) Read- Read-out of the desired flow temperature. - - - : The floor drying process is not active Value: The floor drying process is active Push the dial to: •...
Page 9
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program 10512 Prog. execution (Program execution) Start or stop the floor drying process. Press and hold the dial for 5 seconds in order to start or stop the If the ECL Comfort controller is set to manual mode, the floor drying process.
Page 10
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program 10903 Ramp X5 - X6 (Temperature ramping from time X5 10904 to X6) Ramp X7 - X8 (Temperature ramping from time X7 to X8) Setting the number of steps for the change of the desired flow temperature in selected period.
Page 11
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program 10930 X1 (Start time for period 1) 10931 X2 (Start time for period 2) 10932 X3 (Start time for period 3) If the functional heating period should not be used, X4 can be set 0...
Page 12
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program 10934 X5 (Start time for period 5) 10935 X6 (Start time for period 6) 10936 X7 (Start time for period 7) When X5 is set to a time value, the desired flow temperature starts...
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program 4.0 ECL Tool 4.1 Data logging for report with ECL Tool By means of the ECL Tool a data log can be read from the ECL Version information, example: Comfort controller in order to document the process.
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program 4.2 Short get-going instruction After having established connection between the PC and the ECL controller, the "Load standard parameters (recommended)" is selected. All parameters and settings are listed in groups.