Danfoss ECL Comfort 210 Operating Manual page 59

Application a237/a337
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A237/A337
External signal for desired flow temperature
A voltage (0 - 10 V) can be applied to the input terminal S10 in
order to determine the desired flow temperature.
The measured voltage on input S10 must be converted to a
temperature value by the controller. When the voltage gets higher,
the desired flow temperature increases.
The following settings set up the scaling.
MENU > Settings > Flow temperature / Inlet temperature
Ext. desired T — (ECL Comfort 310)
Circuit
1
The actual desired flow temperature is indicated by the unit °C.
Read-out:
- - :
External voltage signal is not connected..
°C :
External voltage signal converted to desired flow
temperature.
Push the dial to see the graph and enter the value sets for the input
voltage (1 and 10 volt) and displayed desired flow temperature.
Desired flow temperature:
Fixed voltage settings:
Factory settings:
This means that the 'Desired flow temperature' is 10 °C at 1.0 V
and 100 °C at 10 V.
Typically, the higher the voltage, the higher the displayed desired
flow temperature.
VI.LG.R3.02
Factory setting
Setting range
Read-out only
10 ... 120 °C
1 V and 10 V
(1,10) and (10,100)
Example: Relationship between input voltage and displayed desired flow
temperature
Desired flow temp. (°C)
This example shows that 1 volt corresponds to 10.0 °C and 10 volt
correspond to 100 °C.
The external voltage signal must be higher than 1.0 V in order to
activate the override.
Volt
© Danfoss | 2017.05 | 59

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl comfort296Ecl comfort 310

Table of Contents