5 Installation
5.3 Interfaces
Wiring
RS485-topology
50
Screened twisted-pair cables must be used.
Cable specifications
Rated surge impedance
Permissible surge impedance
Max. cable length
Possible baud rates
Tab. 24 Cable specifications
When preparing the cables, ensure that there is a low-resistance connection between
the cable screen and the connector casing ( Chapter 5.3.2,  30).
A bus segment can interconnect up to 32 slaves.
Several bus segments can be connected using repeaters (bi-directional amplifiers). Refer to the
documentation of the repeater manufacturer for more specific details.
The use of repeaters enables the maximum cable length to be increased. Refer to the
documentation of the repeater manufacturer for more specific details.
A bus segment must be provided with cable termination (120 ) at both ends. These terminals
must be connected in the connector directly between pin 3 and 7.
The bus segment must be terminated at both ends.
No more than two terminations must be provided for each bus segment.
Operation without correct cable termination can cause transfer errors.
1
6
2
7
A
120
3
B
8
4
9
5
GND
Fig.. 26 Bus segment with four nodes
HMI/PLC XV-102 08/2016 MN04802004Z-EN www.eaton.com
120 
108...132 
1200 m
9600 Bit/s
19200 Bit/s
38400 Bit/s
57600 Bit/s
115200 bit/s
1
6
2
7
A
A
3
B
B
8
4
9
5
GND
GND
GND
1
1
6
2
2
7
A
A
A
3
3
B
B
B
8
4
4
9
5
5
GND
GND
6
7
120
8
9