Eaton XV-102 Operating Instructions Manual page 33

Touch display
Hide thumbs Also See for XV-102:
Table of Contents

Advertisement

Radio interference
suppression filter for the
24 V DC supply
Additional interference filters must be installed for the power supply in order to adhere to the EMC B
provisions.
Integrate a radio interference suppression filter into the wiring.
Depending on the output, the following filters can be used:
XT-FIL-1 radio interference suppression filter for 24 V DC supply up to 2.2 A (Eaton article no.
285316)
or
XT-FIL-2 radio interference suppression filter for 24 V DC supply up to 12 A (Eaton article no.
118980)
Fig.. 12 Power supply with EMC filter
Grounding is ensured either by using
the filter's integrated contact fields onto a grounded metal plate
or using
a separate line to the filer's PE connection.
Depending on the current consumption or configuration, several filters may be used as well.
2.7 Marine approvals,  14
5.2.2 Conditions for marine approval (DNV GL),  25
5.4.2 Screening the communication cables used,  56
HMI/PLC XV-102 08/2016 MN04802004Z-EN www.eaton.com
L1
L2
L3
N
PE
~
=
0 V
0 V
XT-FIL-1/2
0 V
0 V
0 V
U
U
POW
AUX
XV-102
5 Installation
5.3 Interfaces
0 V
...
33