9 Technical data
9.5 Interfaces
9.5.2
9.5.2.1
74
SmartWire-DT Master

POW/AUX (power supply interface for SmartWire-DT)

Property
Supply voltage U
(control voltage for contactor coils)
Aux
Operational voltage
Rated operating voltage
Permissible voltage
Input voltage residual ripple
Protection against polarity reversal
Current
In accordance with DIN VDE 0641, Part 11
and IEC/EN 60898
In accordance with UL 508
and CSA-22.2, No. 14
Short-circuit rating
Heat dissipation
Potential isolation
Rated operating voltage of
24 V DC slaves
Supply voltage U
(for SmartWire-DT slaves)
Pow
Specifications for connection to supply voltage
Rated operating voltage
Permissible voltage
Input voltage residual ripple
Protection against polarity reversal
Current
Overload proof
Inrush current and length
Heat dissipation at 24 VDC
Potential isolation between U
15 V SmartWire-DT supply voltage
Bridging voltage dips
HMI/PLC XV-102 08/2016 MN04802004Z-EN www.eaton.com
XV-102
24 VDC
Effective:
20.4...28.8 V DC (rated operating voltage -15 % /
+20 %)
Max. 5 %
Yes
Max. 3 A
Max. 2 A
No, external protection required
(e.g. FAZ Z3,  Chapter 5.3.8.3,  39)
Normally 1 W
No
Normally U
24 VDC
Effective:
20.4...28.8 V DC (rated operating voltage -15 % /
+20 %)
Max. 5 %
Yes
Max. 0.7 A
Yes
12.5 A/6 ms
1.0 W
and
No
Pow
10 ms
1)
1)
- 0.2 V
Aux