5
5.1
5.2
5.2.1
5.2.2
Installation
Safety regulations
Read Chapter 3 Safety regulations, 15 before installing and commissioning the de-
vice. This contains important information for your personal safety.
Prerequisites for the location of use
Approvals:
The device must be used exclusively in locations for which it has been approved/certified. See the
markings on the nameplate and Chapter 9 Technical data, 67.
Power supply:
The power supply must comply with the requirements stated in Chapter 9.5.1 Power supply, 73.
Engineering conditions of acceptability by Underwriters Laboratories Inc. (UL)
For the approval in accordance with the standard UL 508, consideration must be given to the following:
Ambient conditions:
Max. ambient air temperature: 50°C
Degree of pollution 2
The screw terminals of the connector for the power supply must be tightened with a max. tightening
torque of 0.6...0.8 Nm or 5...7 Lb. In.
Only XV-102-BE-...- and XV-102-E... devices:
The SmartWire-DT master interface's U
overcurrent and short-circuits with the following:
Miniature circuit-breaker 24 VDC, rated operational current 2 A, tripping characteristic Z
Or a 2 A fuse
Conditions for marine approval (DNV GL)
The following DNV GL rules for shipping classification in accordance with DNVGL-CG-0339 type
approvals must be observed:
1
Complete and proper installation and commissioning in accordance with DNV GL rules and Eaton
requirements and specifications.
2
Installation of radio interference suppression filters for the 24 V DC supply.
3
Screening the communication cables used.
2.7 Marine approvals, 14
5.3.3 Section Radio interference suppression filter for the 24 V DC
supply, 33
5.4.2 Screening the communication cables used, 56
HMI/PLC XV-102 08/2016 MN04802004Z-EN www.eaton.com
supply voltage must be externally protected against
Aux
5 Installation
5.1 Safety regulations
25