Power Supply - Eaton XV-102 Operating Instructions Manual

Touch display
Hide thumbs Also See for XV-102:
Table of Contents

Advertisement

5 Installation
5.3 Interfaces
5.3.3
Wiring
32

Power supply

The device has an internal fuse and protection against polarity reversal. The functional earth is
connected to the connector cover only, and not to 0 V.
The housing is made of plastic and is potential-free. The device's power supply is not galvanically
isolated.
The device requires a power supply of 24 V DC from an AC/DC transformer with safe isolation (SELV).
Additional properties of the required power supply, see chapter 9.5.1 Power supply,  73.
SELV (safety extra low voltage):
Circuit in which no dangerous voltage is present, even in the event of a single fault.
Fig.. 10 Power supply interface
Plug connector Phoenix Contact MSTB 2.5/3-ST-5.08, Phoenix Art no. 1757022 is supplied with
the device.
Fig.. 11 Phoenix Contact MSTB 2.5/3-ST-5.08 plug connector (view from wiring side)
Connection
+24 VDC
0 V
Tab. 7 Plug connection configuration
Observe the following when preparing the wiring of the plug connector:
Terminating the wiring with the plug connector
Terminal type:
Cross section
Strip length
Max. tightening torque
Tab. 8 Terminating the wiring with the plug connector
HMI/PLC XV-102 08/2016 MN04802004Z-EN www.eaton.com
+24 VDC
0 V
Configuration
Supply voltage +24 VDC
Functional earth with connector panel.
Does not have to be connected.
If required due to the installation environment, this connection can be
used as a protective earth connection.
Supply voltage 0 V
Screw terminal plug-in
2
min. 0.75 mm
/ max. 2.5 mm
min. AWG18 / max. AWG12
7 mm
0.6...0.8 Nm / 5...7 Lb. In.
2
(drain wire or conductor)