9.5.2.2
Property
Repetition rate
Status indication
Tab. 36 POW/AUX (power supply interface for SmartWire-DT)
1) 1) If contactors and/or motor starters with a total current draw > 3 A (DIN VDE 0641, Part 11 and IEC/EN 60898) or > 2 A (UL
508 and CSA-22.2, No. 14) are connected, an EU5C-SWD-PF1 or EU5C-SWD-PF2 power feeder module needs to be used.

SWD (SmartWire-DT interface)

Property
SmartWire-DT supply voltage U
Rated operating voltage (internally converted
supply voltage U
)
POW
Current
Short-circuit rating
Number of SmartWire-DT modules on the Smart-
Wire-DT network
SmartWire-DT module address setting
Baud Rate
Tab. 37 SWD (SmartWire-DT interface)
1) If SmartWire-DT modules with a total current draw > 0.7 A are connected,
an EU5C-SWD-PF2 power feeder module needs to be used.
HMI/PLC XV-102 08/2016 MN04802004Z-EN www.eaton.com
XV-102
1 s
Yes (LEDs)
XV-102
VP
14.5 V DC ±3 % (14.0...15.0 VDC)
Max. 0.7 A
Yes
Max. 99
Automatic
125 kbit/s
250 kBit/s
(= default settings)
9 Technical data
9.5 Interfaces
1)