Requirements For The Mounting Position - Eaton XV-102 Operating Instructions Manual

Touch display
Hide thumbs Also See for XV-102:
Table of Contents

Advertisement

5 Installation
5.2 Prerequisites for the location of use
5.2.3
26

Requirements for the mounting position

The device is designed for mounting in control cabinets, control panels or control desks. It can be
mounted horizontally or vertically. The following requirements must be fulfilled when selecting a suitable
mounting position:
The device should not be exposed to direct sunlight (when exposed to UV light, plastic parts of the
device can embrittle and the lifespan of the device is reduced).
If the device is to be used in potentially explosive atmospheres, the device must not be subjected
to hazardous knocks.
The inclination angle for vertical mounting without forced ventilation must be max. ±45°.
The operating elements on the service side of the device and the cable connections are accessible
after the device has been mounted.
The ambient conditions stated must be observed.
See chapter 9.9 Environmental conditions,  78.
Sufficient ventilation (cooling) must be ensured by means of:
Clearance of at least 3 cm to the ventilation slots
Clearance of at least 15 cm from heat radiating components such as heavily loaded trans-
formers
The expected temperatures should be within the permissible range.
See chapter 9.9 Environmental conditions,  78.
Mounting surface characteristics:
Material thickness at the mounting cutout 2...5 mm
Flatness  0.5 mm
(this requirement must also be fulfilled when the device is mounted!)
Surface roughness Rz  120
HMI/PLC XV-102 08/2016 MN04802004Z-EN www.eaton.com