Advertisement

5 Installation
5.3 Interfaces
Wiring
44
Screened twisted-pair cables must be used.
Cable specifications
Rated surge impedance
Permissible surge impedance
Capacitance per unit length
Core cross-section / max. cable length
Tab. 18 Cable specifications
The maximal baud rate depends on the cable length
Cable length
25 m
50 m
100 m
250 m
500 m
500 m
1000 m
2500 m
5000 m
Tab. 19 Relationship of cable length / baud rate
The use of repeaters is recommended for cable lengths over 1000 m. Repeaters can
also be used to implement galvanic isolation. Refer to the documentation of the re-
peater manufacturer for more specific details.
Observe the recommendations of CiA (CAN in Automation).
When preparing the cables, ensure that there is a low-resistance connection between
the cable screen and the connector casing ( Chapter 5.3.2,  30).
HMI/PLC XV-102 08/2016 MN04802004Z-EN www.eaton.com
120 
108...132 
< 60 pF/m
2
 0.25 mm
/ 100 m
2
 0.34 mm
/ 250 m
2
 0.75 mm
/ 500 m
Max. baud rate
1000 kbit/s
800 kbit/s
500 kbit/s
250 kbit/s
125 kbit/s
100 Kbit/s (adjustable via software)
50 kbit/s
20 kbit/s
10 kbit/s