Rs232 (System Port) - Eaton XV-102 Operating Instructions Manual

Touch display
Hide thumbs Also See for XV-102:
Table of Contents

Advertisement

5 Installation
5.3 Interfaces
5.3.4
Wiring
34

RS232 (System Port)

The RS232 interface is not galvanically isolated.
CAUTION
Non-galvanically-isolated interfaces
The device may be damaged by potential differences.
The GND terminals of all bus modules must be connected.
Fig.. 13 RS232 interface (9-pin, D-Sub, male, UNC)
Pin
Signal
1
DCD
2
RxD
3
TxD
4
DTR
5
GND
6
DSR
7
RTS
8
CTS
9
RI
Tab. 9 Pin assignment of the RS232 interface
Screened cables must be used.
The maximal baud rate depends on the cable length
Cable length
2.5 m
5 m
10 m
15 m
30 m
Tab. 10 Relationship of cable length / baud rate
When preparing the cables, ensure that there is a low-resistance connection between
the cable screen and the connector casing ( Chapter 5.3.2,  30).
HMI/PLC XV-102 08/2016 MN04802004Z-EN www.eaton.com
1
2
3
4
5
6
7
8
9
Configuration
Data Carrier Detected
Receive Data
Transmit Data
Data Terminal Ready
Ground
Data Set Ready
Request to Send
Clear To Send
Ring Indicator
Max. baud rate
115200 bit/s
57600 Bit/s
38400 Bit/s
19200 Bit/s
9600 Bit/s