Wiring
Screened twisted pair cables, cable type A (in accordance with Profibus standards IEC/EN 61158
and IEC/EN 61784) must be used.
Cable specifications
Rated surge impedance
Permissible surge impedance
Capacitance per unit length
Loop resistance
Core cross section
Tab. 21 Cable specifications
The maximal baud rate depends on the cable length
Cable length
200 m
400 m
1000 m
1200 m
Tab. 22 Relationship of cable length / baud rate (for cables compliant with cable type A of the Profibus standard IEC/EN 61158
and IEC/EN 61784)
When preparing the cables, ensure that there is a low-resistance connection between
the cable screen and the connector casing ( Chapter 5.3.2,  30).
HMI/PLC XV-102 08/2016 MN04802004Z-EN www.eaton.com
150 
135...165 
< 30 pF/m
< 110 /km
2
 0.34 mm
(22 AWG)
Max. baud rate
1500 kbit/s
500 kbit/s
187.5 kbit/s
 93.75 kbit/s
5 Installation
5.3 Interfaces
47