Configuration Setting - ABB RELION 670 Series Applications Manual

Line differential protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 505 343-UEN B
BC12CLTR (sect.1)
DCCLTR (A1A2)
DCCLTR (B1B2)
BC12CLTR (sect.2)
VPBC12TR (sect.1)
VPDCTR (A1A2)
VPDCTR (B1B2)
VPBC12TR (sect.2)
BC17OPTR (sect.1)
DCOPTR (A1A2)
BC17OPTR (sect.2)
BC17CLTR (sect.1)
DCCLTR (A1A2)
BC17CLTR (sect.2)
VPBC17TR (sect.1)
VPDCTR (A1A2)
VPBC17TR (sect.2)
BC27OPTR (sect.1)
DCOPTR (B1B2)
BC27OPTR (sect.2)
BC27CLTR (sect.1)
DCCLTR (B1B2)
BC27CLTR (sect.2)
VPBC27TR (sect.1)
VPDCTR (B1B2)
VPBC27TR (sect.2)
EXDU_BC (sect.1)
EXDU_DC (A1A2)
EXDU_DC (B1B2)
EXDU_BC (sect.2)
IEC04000480 V1 EN-US
Figure 334: Signals to a line bay in section 1 from the bus-coupler bays in each section
For a line bay in section 2, the same conditions as above are valid by changing section 1 to
section 2 and vice versa.
14.4.2.4

Configuration setting

If there is no bypass busbar and therefore no QB7 disconnector, then the interlocking for QB7
is not used. The states for QB7, QC71, BB7_D, BC_17, BC_27 are set to open by setting the
appropriate module inputs as follows. In the functional block diagram, 0 and 1 are designated
0=FALSE and 1=TRUE:
QB7_OP = 1
QB7_CL = 0
Application manual
BC_12_CL
>1
&
VP_BC_12
&
BC_17_OP
&
>1
BC_17_CL
>1
&
VP_BC_17
&
BC_27_OP
&
>1
BC_27_CL
>1
&
VP_BC_27
&
EXDU_BC
&
en04000480.vsd
Section 14
Control
M13560-108 v4
565