Bay Control Qcbay - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UEN A
14.3.1.1
Bay control REC670 2.2 IEC
Application manual
Accepted originator categories for PSTO
If the requested command is accepted by the authority control, the value will
change. Otherwise the attribute blocked-by-switching-hierarchy is set in the cause
signal. If the PSTO value is changed during a command, then the command is
aborted.
The accepted originator categories for each PSTO value are shown in
Table 33:
Accepted originator categories for each PSTO
Permitted Source To Operate
0 = Off
1 = Local
2 = Remote
3 = Faulty
4 = Not in use
5 = All
6 = Station
7 = Remote
PSTO = All, then it is no priority between operator places. All operator places are
allowed to operate.
According to IEC 61850 standard the orCat attribute in originator category are
defined in
Table 34
Table 34:
orCat attribute according to IE C61850
Value
Description
0
not-supported
1
bay-control
2
station-control
3
remote-control
4
automatic-bay
5
automatic-station
6
automatic-remote
7
maintenance
8
process

Bay control QCBAY

The Bay control (QCBAY) is used to handle the selection of the operator place per
bay. The function gives permission to operate from two main types of locations
either from Remote (for example, control centre or station HMI) or from Local
Originator (orCat)
4,5,6
1,4,5,6
2,3,4,5,6
4,5,6
4,5,6
1,2,3,4,5,6
2,4,5,6
3,4,5,6
Section 14
Control
Table
33.
M16595-3 v9
331

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents