Trip
HF25
Current feedback offset error
225
Hardware fault - return drive to supplier
HF26
Soft start relay failed to close, soft start monitor failed or braking IGBT short circuit at power up
226
Hardware fault - return drive to supplier
HF27
Power stage thermistor 1 fault
227
Hardware fault - return drive to supplier
HF29
Control board thermistor fault
229
Hardware fault - return drive to supplier
HF30
DCCT wire break trip from power module
230
Hardware fault - return drive to supplier
It.AC
Output current overload timed out (I
Ensure the load is not jammed / sticking
Ensure that the motor rated current is not set to zero
Check the load on the motor has not changed If seen during an autotune in servo mode, ensure that the motor rated current Pr 0.46
20
(Pr 5.07) or Pr 21.07 is current rating of the drive
Tune the rated speed parameter
Check feedback device signal for noise
Check the feedback device mechanical coupling
It.br
Braking resistor overload timed out (I
Ensure the values entered in Pr 10.30 and Pr 10.31 are correct
Increase the power rating of the braking resistor and change Pr 10.30 and Pr 10.31
19
If an external thermal protection device is being used and the braking resistor software overload is not required, set Pr 10.30 or
Pr 10.31 to 0 to disable the trip
O.CtL
Drive control board over temperature
Check enclosure / drive fans are still functioning correctly
Check enclosure ventilation paths
23
Check enclosure door filters
Check ambient temperature
Reduce drive switching frequency
O.ht1
Power device over temperature based on thermal model
Reduce drive switching frequency
Reduce duty cycle
21
Decrease acceleration / deceleration rates
Reduce motor load
O.ht2
Heatsink over temperature
Check enclosure / drive fans are still functioning correctly
Check enclosure ventilation paths
Check enclosure door filters
Increase ventilation
22
Decrease acceleration / deceleration rates
Reduce drive switching frequency
Reduce duty cycle
Reduce motor load
O.ht3
Drive over-temperature based on thermal model
The drive will attempt to stop the motor before tripping. If the motor does not stop in 10s the drive trips immediately.
Check DC bus ripple
27
Decrease acceleration / deceleration rates
Reduce duty cycle
Reduce motor load
186
Electrical
Getting
Basic
installation
started
parameters
2
t) - accumulator value can be seen in Pr 4.19
2
t) – accumulator value can be seen in Pr 10.39
www.controltechniques.com
Running the
SMARTCARD
Optimization
motor
Operation
Diagnosis
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
Data
Digitax ST User Guide
UL listing
information
Issue: 3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents