5.9.2
Communications set-up parameters
The following parameters need to be set according to the system
requirements.
0.35 {11.24}
Serial mode
RW
Txt
AnSI (0)
rtU (1)
This parameter defines the communications protocol used by the 485
comms port on the drive. This parameter can be changed via the drive
keypad, via a Solutions Module or via the comms interface itself. If it is
changed via the comms interface, the response to the command uses
the original protocol. The master should wait at least 20ms before send a
new message using the new protocol. (Note: ANSI uses 7 data bits, 1
stop bit and even parity; Modbus RTU uses 8 data bits, 2 stops bits and
no parity.)
Comms value
String
0
AnSI
1
rtU
2
Lcd
ANSIx3.28 protocol
Full details of the CT ANSI communications protocol are given in the
Advanced User Guide.
Modbus RTU protocol
Full details of the CT implementation of Modbus RTU are given in the
Advanced User Guide.
Modbus RTU protocol, but with an SM-Keypad Plus only
This setting is used for disabling communications access when the -
Keypad Plus is used as a hardware key. See the Advanced User Guide
for more details.
0.36 {11.25}
Serial communications baud rate
RW
Txt
300 (0), 600 (1), 1200 (2),
2400 (3), 4800 (4), 9600 (5),
19200 (6), 38400 (7),
57600 (8)*, 115200 (9)*
* only applicable to Modbus RTU mode
This parameter can be changed via the drive keypad, via a Solutions
Module or via the comms interface itself. If it is changed via the comms
interface, the response to the command uses the original baud rate. The
master should wait at least 20ms before sending a new message using
the new baud rate.
NOTE
When using the CT EIA232 Comms cable the available baud rate is
limited to 19.2k baud.
0.37 {11.23}
Serial communications address
RW
Txt
0 to 247
Used to define the unique address for the drive for the serial interface.
The drive is always a slave.
Modbus RTU
When the Modbus RTU protocol is used addresses between 0 and 247
are permitted. Address 0 is used to globally address all slaves, and so
this address should not be set in this parameter
ANSI
When the ANSI protocol is used the first digit is the group and the
second digit is the address within a group. The maximum permitted
group number is 9 and the maximum permitted address within a group is
Digitax ST User Guide
Issue: 3
Electrical
Getting
Basic
installation
started
parameters
US
rtU (1)
Communications mode
ANSI
Modbus RTU protocol
Modbus RTU protocol, but with an
Keypad Plus only
US
19200 (6)
US
1
www.controltechniques.com
Running the
SMARTCARD
Optimization
motor
Operation
9. Therefore, Pr 0.37 is limited to 99 in this mode. The value 00 is used
to globally address all slaves on the system, and x0 is used to address
all slaves of group x, therefore these addresses should not be set in this
parameter.