Model Code [Bfm #30 (1Eh)] - Mitsubishi FX3UC SERIES User Manual

Hide thumbs Also See for FX3UC SERIES:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3UC
User's Manual - Hardware Edition
Bit
Function
RD station
b6
setting error
b7
EEPROM error
DIP switch
b8
changed
b9 to b14
b15
Hardware error

9.18.12 Model code [BFM #30 (1Eh)]

The model code (K7120) of the Built-in master is stored here.
Description
Turns ON when a RD station is connected to
a station number outside the range No. 49 to
No. 64.
Turns ON when a RD station is used in 4-
point mode.
Turns ON when a RD station is connected to
a station number outside the range No. 49 to
No. 64.
Turns ON when a RD station is used in 4-
point mode.
Turns ON when the DIP switch setting is
changed during operation.
-
Prohibited to use
Turns ON when an abnormality is detected
in the self-loop-back test.
9 CC-Link/LT Built-in master ability (Only FX3UC-32MT-LT)
Error flag restoration operation
When the cause of the error is eliminated
and the power is reset, the error flag is
automatically restored.
In the case that a request to write to the
EEPROM is given in any mode other than
CONFIG
mode,
automatically restored when the request to
write to the EEPROM is cleared.
In the case of EEPROM write error or read
error, the error flag is not restored.
When the DIP switch setting is returned to
original status at the time of power ON, the
error flag is automatically restored.
If the DIP switch setting must be changed,
reset the power.
This error flag is not restored because
something is wrong with the hardware.
9.18 Details of buffer memory
the
error
flag
is
-
315
1
2
3
4
5
6
7
8
9
10