2. Countermeasures (addition of power adapter (CL1PAD1))
When the current consumption exceeds 0.35A, add the power supply adapter or dedicated power supply, and
construct the system so that the total current consumption of stations connected to the built-in power supply is
0.35A or less.
For the dedicated power supply and power supply adapter, refer to the manual of power supply adapter.
System configuration example when one power adapter is used
FX
-32MT-LT
3
UC
(Built-in master+
Built-in power supply)
Terminating
resistor
Power supply
0.5m
0.5m
0.5m
0.5m
1) Current consumption calculation
Total current consumption in the built-in power supply
60mA
60mA
station
station
a)
b)
Total current consumption in the power adapter
100mA
150mA
station
station
e)
2) Voltage drop calculation
Voltage drop in the built-in power supply
(7.5m (24'7")
Maximum distance : From the main unit to the farthest station, station d)
3m (9'10")
Voltage drop in the power adapter
(7m (22'11")
Maximum distance : From the power adapter to the farthest station, station h)
0.5m (1'7")
3) Confirmation related to the minimum operating voltage (20.4V DC) of the module
Built-in power supply:24V - 2.3V
Power adapter
From 1), 2) and 3) above, the system cannot be configured using only built-in
power supply regard to both the current restrictions.
Add a power adapter or dedicated power supply.
24V DC
General-purpose
power supply
18m
Station a)
60mA
Station b)
60mA
Station c)
100mA
Station d)
100mA
100mA
100mA
320mA
station
station
c)
d)
150mA
600mA
1000mA
station
station
f)
g)
h)
Constant : 55)
Constant : 0.06
1m (3'3")
1m (3'3")
Constant : 11)
Constant : 0.06
2m (6'6")
1m (3'3")
=
21.7V
=
: 24V - 1.08V
22.92V
9 CC-Link/LT Built-in master ability (Only FX3UC-32MT-LT)
9.6 Selection of the power supply for CC-Link/LT
- The current consumption of each station shall include the current
consumption of the connected I/O equipment.
- It is assumed that the general-purpose power supply satisfies the
required condition.
LINK/POWER connector
LINK connector
Power adapter
CL1PAD1
0.32A
0.35A
1A
5A
0.32A
1.1V
1m (3'3")
1m (3'3")
0.5m (1'7")
1A
1.08V
1m (3'3")
1m (3'3")
1m (3'3")
20.4V
20.4
24V DC
General-purpose
power supply
Power supply
2m
0.5m
Terminating
resistor
0.5m
Station e)
100mA
0.5m
Station f)
150mA
0.5m
Station g)
150mA
0.5m
Station h)
600mA
OK!!
OK!!
2.3V
3.6V
OK!!
7.5m (24'7")
OK!!
3.6V
0.5m (1'7")
7m (22'11")
1
2
3
4
5
6
7
8
9
10
269