Station Number Setting Of The Remote I/O Units - Mitsubishi FX3UC SERIES User Manual

Hide thumbs Also See for FX3UC SERIES:
Table of Contents

Advertisement

FX
FX
Series Programmable Controllers
Series Programmable Controllers
3UC
3UC
User's Manual - Hardware Edition
User's Manual - Hardware Edition
9.9.2

Station number setting of the remote I/O units

1
Setting the Station number
Set the station number using the DIP switches for operation setting.
ting, refer to the following contents.
1. Unused station numbers do not cause an error.
If station numbers are not used and a remote I/O station is connected to an unused station number in the
future, however, the I/O numbers. after the added unit are shifted. It is recommended to set serial numbers.
2. It is not necessary to align the order of unit connection from the built-in master with the
station number.
However, note that input (X) and output (Y) numbers are assigned in the order of station number.
3. Use one station number. only once.
Complete the CONFIG mode in reference to Subsection 9.9.3, and change the operation mode to "ONLINE".
282
Main unit
Terminating
(Built-in
resistor
master)
Station
No.1
Main unit
(Built-in
Terminating
master)
resistor
Station
No.1
Input
X20 to
X23
Main unit
Terminating
(Built-in
resistor
master)
Station
No.
1 to 4
9 CC-Link/LT Built-in master ability (Only FX3UC-32MT-LT)
9.9 Setting of CC-Link/LT built-in master and remote I/O units
Unused
Station
numbers
No.3
Station
Station
No.5
No.3
Input
Output
X30 to
Y20 to
X37
Y23
Station
Station
No.
No.3
5 to 8
No. 3 is used
Nos. 7 and 8 are
twice.
used twice
respectively.
For the station number set-
Station
Unused
Station
No.4,5
numbers
No.8
Terminating
resistor
Station
Station
No.4
No.2
Output
Input
- When all remote I/O
Y24 to
X24 to
unit are the 4-point
Y27
X27
type
Terminating
resistor
Station
No.
7 to 10
Terminating
resistor