Appendix A-2-5 Cautions on write during RUN

In FX
PLCs, write during RUN (program changes in the RUN mode) is enabled using the following
3UC
programming tools.
Programming tools supporting write during RUN
Programming tool
GX Developer
FX-PCS/WIN
(-E)
Cautions on write during RUN
Program memories which can be written
in RUN mode
Number of
program steps
which can be
written for circuit
change in RUN
mode
Circuit blocks which cannot be written in
RUN mode
Circuit blocks which require attention on
operation after write during RUN
416
→ For the operating procedure of and cautions on write during RUN,
Version
Supports write during RUN in the instruction and device ranges in FX
Ver.2.00A or later
PLCs Ver.1.00 or later.
Supports write during RUN in the instruction and device ranges in FX
Ver.7.00A or later
PLCs Ver.3.00 or later.
Supports write during RUN in the instruction and device ranges in FX
Ver.8.13P or later
PLCs Ver.1.00 or later.
Supports write during RUN in the instruction and device ranges in FX
Ver.8.18U or later
PLCs Ver.1.30 or later.
Supports write during RUN in the instruction and device ranges in FX
Ver.8.23Z or later
FX
3UC
Supports write during RUN in the instruction and device ranges in FX
Ver.8.29F or later
FX
3UC
Supports write during RUN in the instruction and device ranges in FX
Ver.1.00 or later
PLCs Ver.3.30 or later.
Supports write during RUN in the instruction and device ranges in FX
Ver.2.00 or later
PLCs Ver.1.00 or later.
Supports write during RUN in the instruction and device ranges in FX
Ver.4.20 or later
PLCs Ver.3.00 or later.
Item
Built-in RAM and optional memory cassette (whose write protect switch is
set to OFF)
Ver.2.20 or later
256 steps or less after edition (addition/deletion) (including NOP
• GX Developer
immediately after circuit blocks except final circuit)
Ver.8.23Z or later
Ver.2.20 or less
127 steps or less after edition (addition/deletion) (including NOP
immediately after circuit blocks except final circuit)
• GX Developer
Ver.8.22Y or
127 steps or less after edition (addition/deletion) (including NOP
former
immediately after circuit blocks except final circuit)
• FX-PCS/WIN(-E)
Circuit blocks in which labels P and I are added, deleted or changed in
edited circuits
Circuit blocks in which 1-ms timers (T246 to T249 and T255 to T511) are
added in edited circuits
Circuit blocks in which the following instructions are included in edited
circuits
• Instruction to output high speed counters C235 to C255 (OUT
• SORT2 (FNC149), TBL (FNC152), RBFM (FNC278) and/or WBFM
Avoid write during RUN to a circuit block including the following
instructions during execution. If write during RUN is executed to such a
circuit block, the PLC decelerates and stops pulse output.
DSZR (FNC150), DVIT (FNC151), ZRN (FNC156), PLSV (FNC157)
instruction [with acceleration/deceleration operation], DRVI (FNC158)
and/or DRVA (FNC159) instruction
Avoid write during RUN to a circuit block including the following instruction
during execution. If write during RUN is executed to such a circuit block,
the PLC immediately stops pulse output.
PLSV (FNC157) instruction [without acceleration/deceleration operation]
A Version Information and Peripheral Equipment Connect ability
refer to the manual of the used programming tool.