9.11.6 Number of occupied stations and Link scan time

If the number of stations is equivalent, the link scan time is longer in 16-point mode than in 4-point mode.

9.11.7 Cautions on I/O number assignment

1. I/O operation
The following inputs/outputs do not operate in CONFIG mode.
1) Inputs/outputs in the remote I/O stations connected to the built-in master do not operate.
2) I/O extension units/blocks connected to the PLC do not operate.
2. When an I/O extension block or the FX
future
The I/O numbers in the remote I/O station connected to the built-in master are shifted to positions after the
I/O numbers in the added I/O extension block or FX
I/O numbers in programs.
3. When a remote device station is used
Note that the I/O numbers are shifted forward if the following setting is performed by mistake in specifying a
reserved station
1) The reserved station is set to an I/O station instead of a remote device station (analog unit) by mistake.
2) An analog unit is connected, and X/Y numbers are used.
By operations 1) and 2), an analog unit is activated.
3) "CONFIG" is executed again.
4) The I/O number assignment shifts backward.
The analog unit is accessed in the BFM.
X000 to X017
FX
-32MT-LT
3UC
Built-in master
Y000 to Y017
Station No. 1
Remote I/O
4 input points
X040 to X043
Station No. 1
Remote I/O
station
4 input points
X040 to X043
294
X020 to X037
Input extension
block
FX
-16EX
2NC
-
Terminating
resistor
Station No. 2
Remote I/O
station
station
4 output points
-
-
Y020 to Y023
Terminating
resistor
Station No. 2
Remote I/O
station
4 output points
-
-
Y020 to Y023
9 CC-Link/LT Built-in master ability (Only FX3UC-32MT-LT)
→ For details Data Link Processing Time, refer to Section 9.16.
-64CL-M is added (to the existing system) in the
2N
-64CL-M. In this case, it is also necessary to shift the
2N
1) Reserved station
Station No. 50
No. 49 set as
Remote I/O station
remote I/O station
4 input/output points
(X044 to X063)
X064, X065
-
Y024, Y025
2) Analog unit is
connected.
3) ("CONFIG" is executed again.)
(Reserved station)
Station No. 50
Remote I/O
Analog unit
station
4 input/output
points
(accessed in
4)X044, X045
BFM)
Y024, Y025
9.11 Assignment of I/O numbers
Terminating
resistor
Assigned I/O
numbers are
shifted forward.