Bfm #30: Model Code - Mitsubishi FX3U-4AD User Manual

Fx3g series fx3u series fx3uc series
Hide thumbs Also See for FX3U-4AD:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Analog Control Edition
3G
3U
3UC
FX
-4AD/FX
-4AD (4-channel Analog Input)
3U
3UC

5.4.13 BFM #30: Model code

"K2080" (fixed value) is stored as the model code.
5.4.14 BFM #41 to #44: Offset data / BFM #51 to #54: Gain data
If the input mode is specified in BFM #0, the offset data and the gain data of each channel will be
automatically stored. The initial offset data and gain data are set for each mode as shown in the following
table:
• Offset data:
• Gain data:
1. Reference offset/gain value and initial value set at delivery
Input mode (BFM #0)
Set
value
Voltage input
0
(-10V to +10V:-32000 to +32000)
Voltage input
1
(-10V to +10V:-4000 to +4000)
Voltage input
2
Analog value direct indication mode
(-10V to +10V:-10000 to +10000)
3
Current input (4mA to 20mA:0 to 16000)
4
Current input (4mA to 20mA:0 to 4000)
Current input
5
Analog value direct indication mode
(4mA to 20mA:4000 to 20000)
Current input
6
(-20mA to +20mA:-16000 to +16000)
Current input
7
(-20mA to +20mA:-4000 to +4000)
Current input
8
Analog value direct indication mode
(-20mA to +20mA:-20000 to +20000)
Analog input value when the digital value is "0" (reference offset value)
Analog input value when the digital value is equal to the reference gain value (The
reference gain value depends on the set input mode.)
Description
Offset
(Channels 1 to 4: BFM #41 to
#44)
Reference
Initial value
value
0
0mV
0
0mV
0
0mV
(Data change
(Data change
impossible)
impossible)
0
4000µA
0
4000µA
4000
4000µA
(Data change
(Data change
impossible)
impossible)
0
0µA
0
0µA
0
0µA
(Data change
(Data change
impossible)
impossible)
5 Buffer Memory (BFM)
5.4 Buffer Memory Details
Initial value: K2080
Numeric data type: Decimal (K)
Setting range: See below.
Initial value: See below.
Numeric data type: Decimal (K)
Gain
(Channels 1 to 4: BFM #51 to
#54)
Reference
Initial value
value
16000
5000mV
2000
5000mV
5000
5000mV
(Data change
(Data change
impossible)
impossible)
16000
20000µA
4000
20000µA
20000
20000µA
(Data change
(Data change
impossible)
impossible)
16000
20000µA
4000
20000µA
20000
20000µA
(Data change
(Data change
impossible)
impossible)
B-39
A
B
C
D
E
F
G
H
I
J

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents