Mitsubishi FX3UC SERIES User Manual page 77

Hide thumbs Also See for FX3UC SERIES:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3UC
User's Manual - Hardware Edition
2) Restriction for the 5V DC power supply capacity
Calculate the 5V DC power supply capacity of the main unit or extension power supply unit.
a)Supplier side
FX
-32MT-LT
3UC
b)Consumer side
FX
-232-BD
3U
FX
-485ADP(-MB)
3U
FX
-4AD-ADP
3U
FX
-32EX
2NC
FX
-32EYT
2NC
FX
-16EYR-T
2NC
FX
-16EYR-T
2NC
FX
-4AD
2NC
FX
-CNV-IF
2NC
FX
-10PG
2N
FX
-2LC
2N
FX
-16CCL-M
2N
"a)Supplier side" - "b)Consumer side" = 350mA - 555mA = -205mA
It is necessary to add an extension power supply unit since the capacity on the
consumer side b) is 205mA larger than the capacity on the supplier side a).
3) Restriction for the number of connectable units
a) Expansion board
There is no problem since this configuration includes only 1 expansion board.
b) Special adapter
There is no problem since this configuration includes only 1 special communication
adapter and 1 special analog adapter.
c) Special function unit/block
This configuration includes the following 3 special function units/blocks.
There is no problem since up to 7 special function units/blocks can be connected.
-
FX
2NC
-
FX
-10PG
2N
-
FX
-2LC
2N
d) Other restrictions
In some models, only 1 unit can be connected to the main unit. When connecting 2 or more units, it is
necessary to add an extension power supply unit. (Refer to Subsection 1.10.2.)
This configuration includes the following equipment, which falls under the restriction for
the number of connectable units.
-
FX
2NC
5V DC power supply capacity and current consumption
350mA
20mA
20mA
40mA
15mA
60mA
100mA
50mA
50mA
50mA
0mA
120mA
70mA
0mA
-4AD
-16EYR-T × 2
1.14 Selection Calculation Example 3 for System Configuration
55mA
115mA
215mA
265mA
315mA
1 Outline
365mA
485mA
555mA
NG!!
→ Refer to the next page
OK!!
OK!!
OK!!
NG!!
→ Refer to the next page
71
1
2
3
4
5
6
7
8
9
10

Advertisement

Table of Contents
loading

Table of Contents