Error Status

If an error is detected in the 2AD-BD, the error status data will be stored in the corresponding special data
register.
The following table shows the special data registers that store the error status data:
Special data register
1st board
2nd board
D8268
Check the ON/OFF status of each bit of the error status data register to check the description of the error.
Errors are assigned to the bits as shown in the following table. Create a program to detect errors.
Bit
b0
Channel-1 over-scale detection
b1
Channel-2 over-scale detection
b2
Unused
b3
Unused
b4
EEPROM error
1. Caution regarding use of error status data
If a 2AD-BD hardware error (b6) or 2AD-BD communication data error (b7) is detected, it is necessary to clear
the error status with a program at the next power-on of the PLC.
For this reason, be sure to create the following program:
M8000
Normally ON
M8002
Initial pulse
D8278
Stores the error status data.
→ For a detailed description of the error status, refer to Section 6.5.
Description
FNC 12
D8268
MOV
RST
RST
FNC 12
K4M0
MOV
Description
Bit
b5
Averaging time setting error
b6
2AD-BD hardware error
b7
2AD-BD communication data error
b8 to b15
Unused
-
K4M0
Error status of 1st analog board
M6
b6 = OFF (hardware error)
Error status of 1st analog board
M7
b7 = OFF (communication data error)
D8268
4 Programming