Output Mode (Characteristics) Bfm #0 - Mitsubishi FX3U-4AD User Manual

Fx3g series fx3u series fx3uc series
Hide thumbs Also See for FX3U-4AD:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Analog Control Edition
3G
3U
3UC
FX
-4DA (4-channel Analog Output)
3U
2.4

Output Mode (Characteristics) BFM #0

For the FX
-4DA, there are two types of output characteristics: voltage (-10 to +10V) and current (0 to
3U
20mA, 4 to 20mA) output characteristics. The output characteristics depend on the set output mode as
described below.
1. Voltage output characteristics [-10 to +10V] (Output mode: 0, 1)
Set output mode: 0
Output type: Voltage output
Analog output range: -10 to +10V
Digital input range: -32000 to +32000
Offset/gain adjustment: Possible
Output voltage (V)
10.2
10
Digital
value
-32000
2. Current output characteristics [0 to 20mA] (Output mode: 2, 4)
Set output mode: 2
Output type: Current output
Analog output range: 0 to 20mA
Digital input range: 0 to 32000
Offset/gain adjustment: Possible
Current
output (mA)
20.4
20
0
3. Current Output characteristics [4 to 20mA] (Output mode: 3)
Set output mode: 3
Output type: Current output
Analog output range: 4 to 20mA
Digital input range: 0 to 32000
Offset/gain adjustment: Possible
Current
output (mA)
20.32
20
4
0
E-8
Set output mode: 1
Output type: Voltage output
(Specification of analog value mV)
Analog output range: -10 to +10V
Digital input range: -10000 to +10000
Offset/gain adjustment: Impossible
0
32000
-10
-10.2
Set output mode: 4
Output type: Current output
(Specification of analog value µA)
Analog output range: 0 to 20 mA
Digital input range: 0 to 20000
Offset/gain adjustment: Impossible
32000
32640
Digital value
32000
32640
Digital value
Output voltage (V)
10.2
10
Digital
value
-10000
0
10000
-10
-10.2
Current
output (mA)
20.4
20
0
20000
20400
Digital value
2 Specifications
2.4 Output Mode (Characteristics) BFM #0

Hide quick links:

Advertisement

Table of Contents
loading