Performance Specifications - Mitsubishi FX3U-4AD User Manual

Fx3g series fx3u series fx3uc series
Hide thumbs Also See for FX3U-4AD:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Analog Control Edition
3G
3U
3UC
FX
-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)
3U
2.3

Performance Specifications

Item
Input signal
Rated temperature
range
Digital output
Resolution
Total accuracy
A/D conversion
time
Input
characteristics
Insulation method
Number of I/O
points occupied
Centigrade ( ° C)
Platinum resistance thermometer sensor (2-wire or 3-wire) Pt1000
Nickel resistance thermometer sensor (2-wire or 3-wire) Ni1000
-50 ° C to +250 ° C
Pt1000
-40 ° C to +110 ° C
Ni1000
Pt1000
-500 to +2500
Ni1000
-400 to +1100
Pt1000
0.1 ° C
Ni1000
±0.5% for full scale (when ambient temperature is 25 ° C±5 ° C)
±1.0% for full scale (when ambient temperature is in the range of 0 to 55 ° C)
/FX
Series PLC : 200µs (The data will be updated at every scan time.)
• FX
3U
3UC
• FX
PLC : 250µs (The data will be updated at every scan time.)
3G
→For a detailed description of data update, refer to Section2.4.
-Pt1000
+2560
+2500
-50°C
0
-500
-550
-Ni1000
+1150
+1100
-40°C
0
-400
-450
• The photocoupler is used to insulate the analog input area from the PLC.
• The DC/DC converter is used to insulate the power supply line from the analog input area.
• Channels are not insulated from each other.
(This number is not related to the maximum number of input/output points of the PLC.)
Specifications
JIS C 1604-1997
DIN 43760-1987
Pt1000
Ni1000
Pt1000
Ni1000
Pt1000
Ni1000
-Pt1000
+4920
+4820
-58
+250°C
-Ni1000
+2390
+2300
-40°F
+110°C
0 points
2 Specifications
2.3 Performance Specifications
Fahrenheit ( ° F)
-58 ° F to +482 ° F
-40 ° F to +230 ° F
-580 to +4820
-400 to +2300
0.2 ° F
°F
0
°F
+482
-580
-670
0
+230°F
-400
-490
J-7
A
B
C
D
E
F
G
H
I
J