Averaging Time - Mitsubishi FX3U-4AD User Manual

Fx3g series fx3u series fx3uc series
Hide thumbs Also See for FX3U-4AD:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Analog Control Edition
3G
3U
3UC
FX
-2AD-BD (2-channel analog Input)
3G
4.5

Averaging Time

If the averaging time is set for the 2AD-BD, the average data will be stored as the input data. The averaging
time can be set for each channel.
Set the averaging time in the following special data registers:
Special data register
1st board
D8264
D8265
1. Cautions regarding averaging time setting
• If the averaging time is set to "1", the immediate data is stored to the special data register.
• If the averaging time is set in the range from 2 to 4095, the average value will be calculated to conform to
the set averaging time, and the average value obtained will be stored in the special data register.
• After turning the PLC power on, the current data is stored to special data registers until the number of data
items reaches the set averaging time. After this, the average data will be stored.
• Set the averaging time in the range from 1 to 4095. If the set value is outside the setting range, an error
signal will be output.
2. Program Example
M8000
Normally
ON
D-16
2nd board
D8274
Averaging time for channel-1 data
D8275
Averaging time for channel-2 data
→ For a detailed description of the error status, refer to Section 6.5
FNC 12
K1
MOV
FNC 12
K5
MOV
Description
Sets the averaging time for
channel-1 of the 1st analog
D8264
board to 1.
Sets the averaging time for
channel-2 of the 1st analog
D8265
board to 5.
4 Programming
4.5 Averaging Time
Setting range: 1 to 4095
Initial value: K1
Numeric data type: Decimal (K)