Programming - Mitsubishi FX3U-4AD User Manual

Fx3g series fx3u series fx3uc series
Hide thumbs Also See for FX3U-4AD:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Analog Control Edition
3G
3U
3UC
FX
-4DA-ADP (4-channel analog Output)
3U
4.

Programming

This chapter describes how to create programs that can output the analog data using the 4DA-ADP.
4.1
Writing of D/A Conversion Data
1) The input digital data will be converted into analog data and then output to the terminals.
2) If data is stored in the special devices, the averaging time can be set, and the output mode can be
specified.
3) Special auxiliary relays (10 points) and special data registers (10 points) are assigned automatically
starting from the adapter nearest the main unit.
• FX
, FX
Series PLC
3U
3UC
FX
-4DA
FX
3U
3U
-ADP
-ADP
4th
3rd
D/A
D/A
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter, and so on. In this case, however, do not include the high-
speed input/output special adapter and the communication special adapter.
→ For a detailed description of special device assignment, refer to Section 4.2.
Communi-
cation
-4DA
FX
-4DA
FX
special
3U
-ADP
adapter
2nd
D/A
High-speed
input/output
-4DA
3U
special
-ADP
adapter
1st
Special devices
Special auxiliary relays:
M8260 to M8269
D/A
Special data registers:
D8260 to D8269
Special auxiliary relays:
M8270 to M8279
Special data registers:
D8270 to D8279
Special auxiliary relays:
M8280 to M8289
Special data registers:
D8280 to D8289
Special auxiliary relays:
M8290 to M8299
Special data registers:
D8290 to D8299
4 Programming
4.1 Writing of D/A Conversion Data
FX
/FX
Series PLC
3U
3UC
Sequence
program
F-15
A
B
C
D
E
F
G
H
I
J