PLC User's Manual - Analog Control Edition
3G
3U
3UC
FX
-4DA-ADP (4-channel analog Output)
3U
3.3
Power Supply Line
Connect the 24V DC power supply line of the 4DA-ADP to the 24+ and 24- terminals of the terminal block.
3.3.1
To Connect to the FX
1. To use an External power supply
4DA-ADP
15V
24-
24+
Terminal
block
24V DC
Caution regarding connection of the power supply line:
• Ground the "
grounding terminal of the PLC main unit.
• For the timing of power-on/off when using an external power supply, see the following manual of the PLC
to be connected.
3.3.2
To Connect To the FX
Caution regarding connection of the power supply line:
• For the 24V DC power supply line, be sure to use the same power as the FX
• Ground the "
grounding terminal of the PLC main unit.
, FX
Series PLC
3G
3U
FX
/FX
3G
3U
Series PLC
(Main unit)
Class-D
grounding
" terminal to class-D grounded power supply line (100Ω or less) together with the
→ Refer to the FX
→ Refer to the FX
Series PLC
3UC
FX
4DA-ADP
3UC
(Main unit)
+15V
connector
24-
24+
24-
Terminal
Black
block
24V DC
" terminal to a class-D grounded power supply line (100Ω or less) together with the
2. To use the 24V DC power of the PLC
4DA-ADP
15V
24-
24+
Terminal
block
Series User's Manual - Hardware Edition.
3G
Series User's Manual - Hardware Edition.
3U
Series PLC
FX
Series PLC
2NC
(Input extension
block)
Power
Power
crossover
Power
connector
connector
24-
24+
24-
24+
Red
Green
Black
Red
Class-D
grounding
3 Wiring
3.3 Power Supply Line
FX
/FX
3G
3U
Series PLC
(Main unit)
0V
24V
Class-D
grounding
24+
Series PLC.
3UC
F-13
A
B
C
D
E
F
G
H
I
J