Fx 2N -8Ad - Mitsubishi FX3U-4AD User Manual

Fx3g series fx3u series fx3uc series
Hide thumbs Also See for FX3U-4AD:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Analog Control Edition
3G
3U
3UC
Common Items
4.1.7
FX
-8AD
2N
Specifications
Number of input points
Analog input range
Absolute maximum input
Offset
Gain
Digital output
*4
Resolution
Ambient temperature:
25±5°C
Ambient temperature:
0 to 55°C
Time required for A/D
conversion
*4
Input characteristics
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method
• The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
*1.
Adjustment of the offset or gain value will not affect the resolution. In the direct indication mode, however, the
offset/gain cannot be adjusted.
*2.
The offset and the gain should satisfy the following condition:
1V
(Gain - Offset)
*3.
The offset and the gain should satisfy the following condition:
3mA
(Gain - Offset)
*4.
The resolution and the input/output characteristics depend on the selected mode.
*5.
If 1 or more channels use the thermocouple input(s), the input voltage/current data conversion speed will be
×
"1 ms
number of selected channels."
Voltage input
-10V to +10V DC
(Input resistance: 200 kΩ)
±15V
*1,*2
-10V to +9V
*1,*2
-9V to +10V
With sign, 15 bits, binary
0.63mV(20V×1/32000)
2.5mV(20V×1/8000)
±0.3%(±60mV) for 20V full scale
±0.5%(±100mV) for 20V full scale
500µs × number of selected channels
When the input mode is set to "0":
+16320
+16000
-10V
0
+10V
-16000
-16320
30mA
4 Comparison of Performance Specifications
FX
-8AD
2N
Current input
8ch
-20mA to +20mA DC
4mA to 20mA DC
(Input resistance: 250 Ω)
±30mA
-20mA to +17mA
-17mA to +30mA
With sign, 14 bits, binary
2.50µA(40mA×1/16000)
2.00µA(16mA×1/8000)
±0.3%(±120µA) for 40mA full scale
Same accuracy for 4mA to 20mA input
±0.5%(±200µA) for 40mA full scale
Same accuracy for 4mA to 20mA input
*5
When the input mode is set to "6":
+8160
+8000
-20mA
0
-8000
Approx.-8160
When the input mode is set to "3":
8200
8000
0
4mA
4.1 Analog Input
A
B
*1,*3
C
*1,*3
D
E
F
+20mA
G
20mA
H
A-27
I
J

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents