Changing of Output Characteristics

The output characteristics can be changed using sequence programs in FX
5.1
Example: Changing of Voltage Output Characteristics
This section describes an example of a program that can change the digital value range from 400 to 2000
(when analog output range is 1 to 5V) to 0 to 10000.
A specified digital value is inputted into D100.
1. Output characteristics
Voltage output characteristics
(product specifications)
10V
5V
1V
0
400
2. Example of program
For example, create the following program to change the digital output data (D100) of the 1st analog board.
M8001
Normally
OFF
FNC 230
D100
LD>=
M10
G-18
2000
4000
Digital value input
FNC 237
K0
D100 K10000
AND<=
FNC 22
D100
MUL
FNC 23
D101
DDIV
FNC 20
D103
ADD
FNC 12
MOV
5.1 Example: Changing of Voltage Output Characteristics
Digital value characteristics
to be changed
Y-axis
2000
(5V)
400
(1V)
0
Desired digital value (D100)
Sets the output mode of 1st board
M8260
to the voltage output mode (0V to 10V).
Sets the output mode to the
M8264
output holding mode.
Check to make sure the digital
M10
value (D100) is in range.
K1600
D101
K10000
D103
Calculation for changing output
characteristics.
Stores the operation result in D8260.
K400
D107
D107
D8260
5 Changing of Output Characteristics
Series PLCs.
3G
X-axis
10000