Specifications - Mitsubishi FX3U-4AD User Manual

Fx3g series fx3u series fx3uc series
Hide thumbs Also See for FX3U-4AD:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Analog Control Edition
3G
3U
3UC
FX
-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)
3U
2.

Specifications

This chapter describes the general, power supply, and performance specifications for the PNK-ADP.
2.1
Generic Specifications
Item
Ambient temperature
Relative humidity
Vibration resistance
Shock resistance
Noise resistance
Dielectric withstand
voltage
Insulation resistance
Grounding
Working
environment
Working altitude
*1.
If PNK-ADP is connected to the FX
*2.
PLC
Independent grounding
Best condition
*3.
If the pressure is higher than the atmospheric pressure, do not use the PNK-ADP.
The PNK-ADP may malfunction.
2.2
Power Supply Specifications
Item
A/D conversion circuit
driving power
Interface driving power
J-6
0 to 55°C (32 to 131°F) when operating
-25 to 75°C (-13 to 167°F) when stored
5 to 95%RH (no condensation) when operating
Frequency
DIN Rail Mounting
57 - 150
*1
Direct Mounting
57 to 150
2
147 m/s
Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y,
and Z
Using noise simulator of:
Noise voltage: 1,000Vp-p / Noise width: 1µs / Rise: 1ns / Cycle: 30 to 100Hz
500 V AC, for 1 min
5MΩ or more using 500V DC
insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
<Common grounding with a heavy electrical system is not allowed.>
Free from corrosive or flammable gas and excessive conductive dusts
*3
< 2000m
3UC
Other
PLC
equipment
equipment
Shared grounding
Good condition
→ For a detailed description of the grounding, refer to Section 3.7.
24V DC +20% -15%, 45mA
(It is necessary to connect a 24V DC power supply to the terminal block.)
5V DC, 15mA
(Since the internal power is supplied from the FX Series main unit, it is not
necessary to supply the power.)
Specifications
Acceleration
2
(Hz)
(m/s
)
10 - 57
-
4.9
10 to 57
9.8
Between batch of all terminals and ground terminal
Series PLC, direct installation is not possible.
Other
Other
PLC
equipment
Common grounding
Not allowed
Specifications
2 Specifications
2.1 Generic Specifications
Half amplitude
(mm)
Tested 10 times in
0.035
each direction (X-, Y-,
and Z-axis directions)
-
(Total: 80 min, each)
0.075
*2