Averaging Time - Mitsubishi FX3U-4AD User Manual

Fx3g series fx3u series fx3uc series
Hide thumbs Also See for FX3U-4AD:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Analog Control Edition
3G
3U
3UC
FX
-4AD-ADP (4-channel analog Input)
3U
4.5

Averaging Time

If the averaging time is set for the 4AD-ADP, the average data will be stored as the input data. The averaging
time can be set for each channel.
Set the averaging time in the following special data registers:
• FX
, FX
3U
3UC
1st
D8264
D8265
D8266
D8267
• FX
Series PLC
3G
Special data register
1st
D8284
D8285
D8286
D8287
1. Cautions regarding averaging time setting
• If the averaging time is set to "1", the immediate data is stored to the special data register.
• If the averaging time is set in the range from 2 to 4095, the average value will be calculated to conform to
the set averaging time, and the average value obtained will be stored in the special data register.
• After turning the PLC power on, the current data is stored to special data registers until the number of data
items reaches the set averaging time. After this, the average data will be stored.
• Set the averaging time in the range from 1 to 4095. If the set value is outside the setting range, an error
signal will be output.
2. Program Example (For FX
M8000
Normally
ON
C-20
Series PLC
Special data register
2nd
3rd
D8274
D8284
D8275
D8285
D8276
D8286
D8277
D8287
2nd
D8294
Averaging time for channel-1 data
D8295
Averaging time for channel-2 data
D8296
Averaging time for channel-3 data
D8297
Averaging time for channel-4 data
→ For a detailed description of the error status, refer to Section 6.5
, FX
3U
3UC
FNC 12
K1
MOV
FNC 12
K5
MOV
4th
D8294
Averaging time for channel-1 data
D8295
Averaging time for channel-2 data
D8296
Averaging time for channel-3 data
D8297
Averaging time for channel-4 data
Description
Series PLC)
Sets the averaging time for
channel-1 of the 1st analog
D8264
special adapter to 1.
Sets the averaging time for
channel-2 of the 1st analog
D8265
special adapter to 5.
4 Programming
4.5 Averaging Time
Setting range: 1 to 4095
Initial value: K1
Numeric data type: Decimal (K)
Description

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents