Replace Modules - GE C30 Instruction Manual

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

REPLACE MODULES

4.
Click the OK button to save the change.
8.5 Replace modules
This section outlines how to replace a module.
The relay, being modular in design, allows for the withdrawal and insertion of modules. Replace modules only with like
modules in their original factory configured slots.
To replace a module:
1.
Open the enhanced faceplate to the left once the thumb screw has been removed. This allows for easy access of the
modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and
allows easy access to all modules in the C30.
The standard faceplate can be opened to the left once the black plastic sliding latch on the right side has been pushed
up, as shown below.
8
8-6
Withdraw or insert a module only when control power has been removed from the unit, and be
sure to insert only the correct module type into a slot, else personal injury, damage to the unit
or connected equipment, or undesired operation can result.
To avoid damage to the equipment, use proper electrostatic discharge protection (for example, a
static strap) when coming in contact with modules while the relay is energized.
Figure 8-4: Modules inside relay with front cover open (enhanced faceplate)
CHAPTER 8: MAINTENANCE
842812A1.CDR