CHAPTER 5: SETTINGS
8BIT SW 1 ARG A0 to 8BIT SW 1 ARG A7
switch. These operands are routed to the output operands if the control input is in the "Off" position.
BIT SW 1 ARG B0 to 8BIT SW 1 ARG B7
switch. These operands are routed to the output operands if the control input is in the "On" position.
— This setting specifies FlexLogic operands to control the routing between the A and B inputs of the
8BIT SW 1 CONTROL
switch. If the control operand is in the "Off" state, the first (A) input is switched to the output. If the control operand is in the
"On" state, the second (B) input is switched to the output. The switching takes place instantaneously.

5.7.6 PID regulator

SETTINGS  CONTROL ELEMENTS  PID REGULATOR  PID 1(4) REGULATOR
 PID 1
 REGULATOR
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
— These settings specify FlexLogic operands that constitute the first (A) input of the
— These settings specify FlexLogic operands that constitute the second (B) input of the
Figure 5-67: 8-bit switch logic
SETTING
8BIT SWITCH 1
FUNCTION:
Enabled = 1
RUN
SETTINGS
8BIT SW 1 ARG A0:
Off = 0
8BIT SW 1 ARG B0:
Off = 0
8BIT SW 1 ARG A1:
Off = 0
8BIT SW 1 ARG B1:
Off = 0
8BIT SW 1 ARG A2:
Off = 0
8BIT SW 1 ARG B2:
Off = 0
8BIT SW 1 ARG A3:
Off = 0
8BIT SW 1 ARG B3:
Off = 0
8BIT SW 1 ARG A4:
Off = 0
8BIT SW 1 ARG B4:
Off = 0
8BIT SW 1 ARG A5:
Off = 0
8BIT SW 1 ARG B5:
Off = 0
8BIT SW 1 ARG A6:
Off = 0
8BIT SW 1 ARG B6:
Off = 0
8BIT SW 1 ARG A7:
Off
Off = 0
8BIT SW 1 ARG B7:
On
Off = 0
SETTING
8BIT SW 1 CONTROL:
Off = 0
PID 1
FUNCTION: Disabled
PID 1 SAMPLE TIME:
0.05 s
PID 1 PROCESS
SIGNAL: Off
FLEXLOGIC OPERAND
8BIT SWITCH 1 BIT 0
FLEXLOGIC OPERAND
8BIT SWITCH 1 BIT 1
FLEXLOGIC OPERAND
8BIT SWITCH 1 BIT 2
FLEXLOGIC OPERAND
8BIT SWITCH 1 BIT 3
FLEXLOGIC OPERAND
8BIT SWITCH 1 BIT 4
FLEXLOGIC OPERAND
8BIT SWITCH 1 BIT 5
FLEXLOGIC OPERAND
8BIT SWITCH 1 BIT 6
FLEXLOGIC OPERAND
8BIT SWITCH 1 BIT 7
842017A1.CDR
Range: Enabled, Disabled
Range: 0.05 to 30.00 s in steps of 0.01
Range: Off, any FlexAnalog parameter
CONTROL ELEMENTS
5
5-145