CHAPTER 6: ACTUAL VALUES
The C30 is provided with optional GOOSE communications capability. This feature is specified as a
software option at the time of ordering. See the Order Codes section of chapter 2 for details.
The RxGOOSE Analog values display in this menu. The RxGOOSE Analog values are received via IEC 61850 GOOSE
messages sent from other devices.
6.3.3 Transducer inputs and outputs
ACTUAL VALUES METERING TRANSDUCER I/O DCMA INPUTS DCMA INPUT xx
DCMA INPUT xx
Actual values for each DCmA input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value followed by the programmed units.
ACTUAL VALUES METERING TRANSDUCER I/O RTD INPUTS RTD INPUT xx
RTD INPUT xx
Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value.
6.4 Records
6.4.1 Event records
ACTUAL VALUES RECORDS EVENT RECORDS
EVENT RECORDS
The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological
order from most recent to oldest. When all 1024 event records have been filled, the oldest record is removed as a new
record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated
with the event trigger. See the
6.4.2 Oscillography
ACTUAL VALUES RECORDS OSCILLOGRAPHY
OSCILLOGRAPHY
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
DCMA INPUT xx
0.000 mA
RTD INPUT xx
-50 °C
EVENT: XXXX
RESET OP(PUSHBUTTON)
EVENT: 3
POWER ON
EVENT: 2
POWER OFF
EVENT: 1
EVENTS CLEARED
COMMANDS
CLEAR RECORDS
FORCE TRIGGER?
No
Date and time stamps
EVENT 3
DATE: 2000/07/14
EVENT 3
TIME: 14:53:00.03405
menu for clearing event records.
Range: No, Yes
RECORDS
6
6-11